1. United States
  2. All 3M Products
  3. Electrical
  4. Power Cable Connectors
  5. Power Cable Terminations
  6. 3M™ Cold Shrink QT-III 3/C Termination Kit 7684-S-8-3G, Tape/Wire/UniShield®, 15-35 kV, Insulation OD 0.92-1.18 in, 3/kit

3M™ Cold Shrink QT-III 3/C Termination Kit 7684-S-8-3G, Tape/Wire/UniShield®, 15-35 kV, Insulation OD 0.92-1.18 in, 3/kit

  • Part Number 7684-S-8-3G
  • 3M ID 7100164756
  • UPC 00054007436867
Voltage 15 kV, 25 kV, 35 kV
Conductor Sizes (Imperial) 1 AWG, 1/0 AWG, 2/0 AWG, 3/0 AWG, 4/0 AWG, 250 kcmil, 300 kcmil, 350 kcmil
Insulation Outer Diameter (Metric) 23.368 mm, 23.622 mm, 23.876 mm, 24.13 mm, 24.384 mm, 24.638 mm, 24.892 mm, 25.146 mm, 25.4 mm, 25.654 mm, 25.908 mm, 26.162 mm, 26.416 mm, 26.67 mm, 26.924 mm, 27.178 mm, 27.432 mm, 27.686 mm, 27.94 mm, 28.194 mm, 28.448 mm, 28.702 mm, 28.956 mm, 29.21 mm, 29.464 mm, 29.718 mm, 29.972 mm
Insulation Outer Diameter (Imperial) 0.92 in, 0.93 in, 0.94 in, 0.95 in, 0.96 in, 0.97 in, 0.98 in, 0.99 in, 1 in, 1.01 in, 1.02 in, 1.03 in, 1.04 in, 1.05 in, 1.06 in, 1.07 in, 1.08 in, 1.09 in, 1.1 in, 1.11 in, 1.12 in, 1.13 in, 1.14 in, 1.15 in, 1.16 in, 1.17 in, 1.18 in
Cable Shielding Tape Shield, Wire Shield, UniShield®
Number of Skirts 8

Provides a void-free seal to tape shield, wire shield and UniShield® power cables

High dielectric-constant material regulates the distribution of electric field stress

Suitable for outdoor applications

View more details

Details

Highlights
  • Provides a void-free seal to tape shield, wire shield and UniShield® power cables
  • High dielectric-constant material regulates the distribution of electric field stress
  • Suitable for outdoor applications
  • Integrated design allows for easier installation, while sealing compounds provide constant radial pressure

3M™ Cold Shrink QT III 7600 S 3G Series Termination Kit includes a skirted, 3 phase termination. It ensures a pliable, tight seal for tape shield, wire shield and UniShield® power cables. The conjunction of high dielectric constant material and sealing compounds allows the termination to withstand voltages of 5 to 35kV.

Typical properties

BIL

200 kV

Brands

3M™

Breakout Boot

Yes

Cable Insulation Outside Diameter Range

0.92-1.18 in

Cable Insulation Outside Diameter Range (Metric)

23.4-30.0 mm

Cable Shielding

Tape Shield, Wire Shield, UniShield®

Case Quantity

1

Conductor Sizes (Imperial)

1 AWG, 1/0 AWG, 2/0 AWG, 3/0 AWG, 4/0 AWG, 250 kcmil, 300 kcmil, 350 kcmil

Indoor/Outdoor

Outdoor Skirted

Insulation Level

100%, 133%

Insulation Outer Diameter (Imperial)

0.92 in, 0.93 in, 0.94 in, 0.95 in, 0.96 in, 0.97 in, 0.98 in, 0.99 in, 1 in, 1.01 in, 1.02 in, 1.03 in, 1.04 in, 1.05 in, 1.06 in, 1.07 in, 1.08 in, 1.09 in, 1.1 in, 1.11 in, 1.12 in, 1.13 in, 1.14 in, 1.15 in, 1.16 in, 1.17 in, 1.18 in

Insulation Outer Diameter (Metric)

23.368 mm, 23.622 mm, 23.876 mm, 24.13 mm, 24.384 mm, 24.638 mm, 24.892 mm, 25.146 mm, 25.4 mm, 25.654 mm, 25.908 mm, 26.162 mm, 26.416 mm, 26.67 mm, 26.924 mm, 27.178 mm, 27.432 mm, 27.686 mm, 27.94 mm, 28.194 mm, 28.448 mm, 28.702 mm, 28.956 mm, 29.21 mm, 29.464 mm, 29.718 mm, 29.972 mm

Insulation Rejacketing

Yes

Lug/Stem Connector Included in Kit

No

Maximum Cable Outside Diameter

3.90 Inch

Maximum Cable Outside Diameter (Metric)

99.1 mm

Maximum Installed Length

20.50 in

Number of Conductors

3

Number of Skirts

8

Product Series

7600-3G

Voltage

15 kV, 25 kV, 35 kV

Voltage Application

Medium Voltage

Resources

Manufacturing Origin: USA

The designation that a product is Manufactured in the USA means the product undergoes substantial transformation in one of our U.S. Manufacturing plants. Some products contain imported components.

Note: 3M products offered on a government contract that require country of origin representation must be certified by 3M Trade Compliance. Contact customer service at 800-245-3573 to request a certificate.
For industrial/occupational use only. Not for consumer sale or use.

3M industrial and occupational products are intended, labeled, and packaged for sale to trained industrial and occupational customers for workplace use.  Unless specifically stated otherwise on the applicable product packaging or literature, these products are not intended, labeled, or packaged for sale to or use by consumers (e.g., for home, personal, primary or secondary school, recreational/sporting, or other uses not described in the applicable product packaging or literature), and must be selected and used in compliance with applicable health and safety regulations and standards (e.g., U.S. OSHA, ANSI), as well as all product literature, user instructions, warnings, and other limitations, and the user must take any action required under any recall, field action, or other product use notice.  Misuse of 3M industrial and occupational products may result in injury, sickness, death, or property damage.  For help with product selection and use, consult your on-site safety professional, industrial hygienist, or other subject matter expert.